1-2.選用適當的電線SELECT THE PROPER CABLE
1-2.選用適當的電線SELECT THE PROPER CABLE
1.如何選用適當捲線器HOW TO SELECT CABLE REEL 下載down load
1-2.選用適當的電線SELECT THE PROPER CABLE
1-3.美國電線直徑和重量及安培數一覽表CABLE DIA AND NET WEIGHT AND AMPERAGE CHART
1-4.問卷表QUESTIONAIRE
IMPORTANT: Due to the great variety of electrical applications , types (and manufacturers) of contro悔,and available currents. it is impossible for the reel manufacturer to select electrical cable for
any specific requirement. As the user. or specifying engineers. are
closest to all details involved in any particular requirement. the re
sponsibility for selecting cable for a specific requirement must be
left in their hands. To assist in the selection of cable. the charts shown on this page and the following procedure are 0行ered as a guide.
For more complete data or specific details. please refer to the
National Electric Code.
To select cable:
(a) Determine motor horsepower (HP).
(b) Using Chart A for Alternating Current (AC) or Chart 8 for Direct
Current (DC). find the proper horsepower in the left hand column.
(c) On the line showing proper horsepower. move to the right until reaching the column headed by the operating voltage to be used. (d) At this intersection the maximum ampere load is listed. For
examp怡. a 100 HP motor. operating at 460 volts three-phase cur
rent,draws 124 amperes.
(e) Once maximum ampere load is known. we can determine the size of electrical cable (AWG) required by using Chart C. In the
above example. 124 amperes calls for #1/0 cable at 60 0 C.; # 1 at
750 C.. etc.
(f) To comply with CSA requirements. Types SOW or WOW must be used on outdoor applications.
(g) Caution: Voltage drop and power factor corrections frequently require an increase in size of conductors required.
USE THE 750 COLUMN FOR STANDARD CABLES. Contact the cable manufacturer or Aero-Motive if higher temperature ratings are required. Temperature ratings in the blue shaded areas are aenerally available on special order.